Fire fighter
Manual control -
Pressure differential Systems (PDS)
System Control – Fire fighters key-lock switch
AUTO: Automatic control through pressure transducer + VSD (default position).
ON: Manual activation of the system with 2 pre-set fan speeds (MIN/MAX). Allows to manually force the MD dampers to open, ignoring the smoke sensor.
OFF: Manual STOP and system reset, ignores external signals.
Main Features
Performance verified in AMCA accredited and ENAC audited laboratory.
Key-lock switch for manual override for fire-fighters (ON/AUTO/OFF), also useful for commissioning stage and maintenance operations.
AUTO/OPEN for damper control, forces its opening ignoring the smoke sensor.
Remote control using PDS REM MD series accessories.
Status indicators: PDS CONTROL OK/FAN ON/FAULT/FIRE/DAMPER OPEN/SMOKE IN DAMPER.
Calibration-friendly for ease of commissioning and routine maintenance operations.
Pre-cabled maneuver for remote activation of daily ventilation, by means of a time programmer.
Outputs for status monitoring.
Modbus protocol communication available.
Modbus notes
Modbus RTU. Necessary to input slave address as a factory setting. Modbus TCP/IP through gateway.
Option 1 - Available as an accessory.
Option 2 - In-built in the unit (upon request).
Steel enclosure.
Models
PDS CONTROL MD for single fan systems with an MD damper.
PDS CONTROL MD2 for single fan systems with two MD dampers.
PDS CONTROL MD DUAL for systems that require a back-up stand-by fan, whether in series or in parallel, and an MD damper.
PDS CONTROL MD2 DUAL for systems that require a back-up stand-by fan, whether in series or in parallel, and two MD dampers.
Supply voltage
M – Single phase; 220-240V 50/60Hz up to 2,2kW.
T – Three phase; 380-500V + N 50/60Hz up to 15kW, depending on the model. Other kW requirements, check with S&P.
Units available in EasyVent and through EasyCalc.