PROTECTION
-
Versions
Range of cylindrical cased axial flow fans fitted with aluminium impellers and manufactured from high grade rolled galvanised steel and protected against corrosion by cataforesis primer and black polyester paint finish.
All models are supplied with pre-wired wiring junction box located on the outside of the fan casing for easy wiring access.
Available, depending upon the model, with single or three phase motors in 2, 4 or 6 poles.
Motors
Single phase motor (TCBB) or three phase motor (TCBT).
Models 250, 315, 355 and 400: External rotor motor, IP44, Class F, thermal protection, working temperature from -40ºC to +40ºC.
Models 450, 500, 560, 630 and 6/710: IP65, Class F, thermal protection, working temperature from -40ºC to +70ºC.
Models 4/710 and 800: IP55, Class F, working temperature from -40ºC to +40ºC.
All motors are speed controllable by autotransformer except models /4-560H, /4-630, 710 and T/800.
Three phase motors are speed controllable by inverter.
Electrical supplies:Single phase 230V-50Hz.
(Capacitor located inside the wiring terminal box).
Three phase 230/400V-50Hz or 400V-50Hz.
(See characteristic chart).
Additional information
Standard air direction: form (B)
configuration
(impeller over motor).
On request
Air direction: form (A) configuration (motor over impeller).
From Ø450 to Ø800, three phase motors 2 speed, 4/8 poles.
All models are supplied with pre-wired wiring junction box located on the outside of the fan casing for easy wiring access.
Available, depending upon the model, with single or three phase motors in 2, 4 or 6 poles.
Motors
Single phase motor (TCBB) or three phase motor (TCBT).
Models 250, 315, 355 and 400: External rotor motor, IP44, Class F, thermal protection, working temperature from -40ºC to +40ºC.
Models 450, 500, 560, 630 and 6/710: IP65, Class F, thermal protection, working temperature from -40ºC to +70ºC.
Models 4/710 and 800: IP55, Class F, working temperature from -40ºC to +40ºC.
All motors are speed controllable by autotransformer except models /4-560H, /4-630, 710 and T/800.
Three phase motors are speed controllable by inverter.
Electrical supplies:
(Capacitor located inside the wiring terminal box).
Three phase 230/400V-50Hz or 400V-50Hz.
(See characteristic chart).
Additional information
Standard air direction: form (B)
configuration
(impeller over motor).
On request
Air direction: form (A) configuration (motor over impeller).
From Ø450 to Ø800, three phase motors 2 speed, 4/8 poles.
Versions TCBT ATEX
Sur demande, versions pour ambiances explosives selon la directive ATEX pour les modèles avec moteur triphasé:
• Température d’utilisation:
De -20°C à +55°C:
modèles TCBT/4-315 à 630 mm
modèles TCBT/4-315 à 630 mm
De -20°C à +40°C:
modèles TCBT/4-710 à 800 mm
modèles TCBT/6-800 mm
• Moteurs IP55, classe F.
• Antidéflagrant ATEX - gaz
Pour les modèles 710 à 800 mm:
II 2G Ex d IIB T4
II 2G Ex d IIB(H2) T4 (avec moteur Ex d IIC T4)
• Sécurité augmentée ATEX - gaz
Non disponible:
TCBT/2-250/H 400V-50Hz
TCBT/4-250/H 400V-50Hz
TCBT/6-355/H 400V-50Hz
TCBT/6-400/H 400V-50Hz
Disponible pour le modèle TCBT/6-400/H 230/400V-50Hz et tailles supérieures.
• ATEX - Poussière
Pour les modèles 800 à 1000 mm
Poussière non-conductrice:
II 3D Ex tc
Sur demande, versions pour ambiances explosives selon la directive ATEX pour les modèles avec moteur triphasé:
• Température d’utilisation:
De -20°C à +55°C:
modèles TCBT/4-315 à 630 mm
modèles TCBT/4-315 à 630 mm
De -20°C à +40°C:
modèles TCBT/4-710 à 800 mm
modèles TCBT/6-800 mm
• Moteurs IP55, classe F.
• Antidéflagrant ATEX - gaz
Pour les modèles 710 à 800 mm:
II 2G Ex d IIB T4
II 2G Ex d IIB(H2) T4 (avec moteur Ex d IIC T4) • Sécurité augmentée ATEX - gaz
Non disponible:
TCBT/2-250/H 400V-50Hz
TCBT/4-250/H 400V-50Hz
TCBT/6-355/H 400V-50Hz
TCBT/6-400/H 400V-50Hz
Disponible pour le modèle TCBT/6-400/H 230/400V-50Hz et tailles supérieures.
• ATEX - Poussière
Pour les modèles 800 à 1000 mm
Poussière non-conductrice:
II 3D Ex tc -
Corrosion resistance
Rolled steel casings and motor support protected by cataforesis primer and black polyester paint finish.
Stainless steel screws. -
Terminal box
Wiring terminal box with cable gland PG-11 (except ATEX models). -
Impeller dynamically balanced
Impellers are dynamically balanced, according to ISO 1940 standard, giving vibration free operation. -
Configuration for models /4-710 and 800.
-
Constructive configuration models 250, 315, 355 and 400.