Heat recovery
-
-
-
-
INPUT FILTER
-
EXTRACTION FILTER
-
HORIZONTAL CONFIGURATION
-
WITH NO ADDITIONAL HEAT INPUT
Circular inlet and outlet flanges with seals in models 500 to 1800, and rectangular flanges in models 2500 to 4500. Available only in a horizontal version.
Minimum outside air temperature -10ºC.
For lower temperatures, it is necessary to use preheating batteries located at the suction of the outside air.
ApplicationsAir renewal in commercial premises, offices, hotels, public buildings, schools.
The CAD-COMPACT range is not available with additional post-heating batteries integrated in the unit, although it is possible to add them as accessories.
FansPlug fans with reverse impeller blades.
Single-phase EC motors with integrated electronic protection. IP44, Class B.
Filters-F7: Low pressure F7 filters (ePM1, 70%) for air supply.
- M5: M5 filters (ePM10, 50%) for air extraction.
- It is possible to mount a second filter inside the system (supplied as an accessory).
Control
CAD-COMPACT units can be supplied with 3 levels of control functioning:
ECOWATT VERSION
BASIC and ADVANCED VERSION
See detailed characteristics of both controls in the table about Plug&Play versions functionalities.
Other data
Single-phase electrical supply 230V 50-60Hz in models 500 to 3200, three-phase 400V 50-60Hz in model 4500.
Nominal airflow of 460 to 4,165 m³/h with 150Pa of available pressure.
All models and versions include internal bypass.
-
BASIC version
Characteristics:
- Remote control included.
- Manual/automatic speed control.
- Manual and automatic bypass control.
- Alarm indication.
- Modbus communication. -
ADVANCED version
Characteristics:
- Touch control screen.
- Same functions as BASIC version plus fan control in VAV, COP and CAV modes.
- Control of external water coils (accessories).
- Additional functions. -
Electrical box included
External security switch included. Both in the pre-wired ECOWATT version and in the BASIC and ADVANCED Plug&Play versions. -
Low noise level and robust construction
Twin panel enclosure. Fireproof thermo-acoustic insulation A1/M0 of 25 or 30 mm thickness, depending on the model. -
Highly efficient heat exchanger made of aluminium (up to 86%) certified by Eurovent.
-
Motors
Plug fans are equipped with single-phase EC motors. -
High-efficiency filters
- Low pressure F7 filters (ePM1, 70%) for air supply.
- M5 filters (ePM10 50%) in the extraction.
Possibility of mounting a second filter inside the unit (supplied as an accessory). -
Bypass
All versions include internal bypass with an integrated actuator. -
Easy assembly
Specific supports for installation in false ceilings.